TopicTwo conveyors in ladder
Title
Two conveyors and a TON
ExampleW10.1
Step1 / 3
Mode
Given
Given
An S7-300 runs the two networks in the screenshot every ms. Start (I 0.0) is pressed at s and let go at s; Stop (I 0.1, a normally closed button) is pressed at s. Fill in conveyor 1 (Q 4.0), the TON's elapsed time ET (MD 20) and conveyor 2 (Q 4.1) after the scan at each time.
- Start on I 0.0, Stop on I 0.1 (normally closed: until pressed)
- the TON in DB 1, PT s, ET in MD 20
| s | I 0.0 | I 0.1 | Q 4.0 | ETms | Q 4.1 |
|---|---|---|---|---|---|
| 0.5 | 0 | 1 | 0 | ||
| 1.0 | 1 | 1 | 1 | ||
| 3.0 | 0 | 1 | 1 | ||
| 6.0 | 0 | 1 | 1 | ||
| 8.0 | 0 | 0 | 0 |
Network 1 latches conveyor 1
Start closes its contact at s and Q 4.0 comes on; from the next scan its own contact Q 4.0 holds the rung, so letting Start go changes nothing. Stop reads until it is pressed: its NO contact opens only at s.
Sim
The two conveyors, running
Press Start and Stop, then run time on. A rung carrying power is inked, the TON's gauge fills as ET counts up to PT, and the timing chart measures the delay from Q 4.0 to Q 4.1.
InputsTime
t = 9.0 s · a scan every 100 ms
Q 4.0 = 0, Q 4.1 = 0
DB 1: ET 0 ms of 5000 ms